Programmable Type Transducers

  • micar2

    MICAR 2

    Programmable digital transducers

    PRODUCT ADVANTAGES

    • Class 0.2 / insulation 4 kV
    • Up to 4 configurable analogue outputs
    • 32 measurable electrical quantities
    • DIN-rail or panel mounting
    • Option of 2 or 4 on-off outputs
    • Communicationand programming via optical head if local or via Ethernet network or RS485 output if remote
    • Electrical network supervision and display of the energy values, harmonics and THD with the E.view+ software

    GENERAL SPECIFICATIONS

    • Quantities measured: 1, 2, 3 or 4 selected among 32 electrical quantities
    • Configuration: at the factory or by the user with the E.view+ software
    • Current inputs: 1 A and 5 A
    • Voltage inputs: 100 to 400 V (ph-ph) or 57.7 to 230 V (ph-N)
    • Transfer curves/strong>: linear, 2 slopes, quadratic
    • Output signal: configurable between – 20 mA and + 20 mA
    • Response time: 350 ms
    • Operating frequency: 50 Hz or 60 Hz
    • Auxiliary power source with wide dynamic range: 80 to 264 Vac/dc or 19 to 57 Vdc
    • Compliance with CE directive

  • TRIAD 2

    TRIAD 2

    • Accuracy up to 0.1% on all measurements
    • Response time programmable down to to 50 ms on each measurement and each analogue channel
    • 200 ms for a class of 0.2%
    • Up to 4 analogue channels
    • Ethernet communication available with ModBus and JBus protocols
    • Overvoltage category or “so-called installation category” III (at 300 Vrms). This means better creepage distances and greater distances in the air between traces, so the cost of the product is greater due to the need to increase the insulating barriers
    • Product with double insulation
    • Test voltage or “so-called insulation voltage” = 4 kV / 50 Hz – 1 min
    • Product configurable at the factory or by the customer with the TRIADJUST 2 software available for download from the ENERDIS website.
    • TRIADJUST 2 easy-to-use software for configuration, display and recording.
    • >Product designed and manufactured IN FRANCE.

    Model T3xy

    • Dimension: 120x80x120.5 mm
    • Measurements on single phase, Three phase balanced or unbalanced networks 3 / 4 wires
    • 0, 1, 2, 3 or 4 analogue output(s)
    • Measurements of V, U, I, F, P, Q, S, FP, Tan φ , Cos φ , φ Fund, φ U, φ V
    • Adjustable accuracy class from 0.1% to 1% (depending on response time)
    • Adjustable response time from 50ms to 1s
    • Ethernet or RS485 communication option
    • Configuration via TRIADJUST 2 software

    Model T1xy

    • Dimension: 60x80x120.5 mm
    • Measurements on single phase or Three phase balanced networks 3 / 4 wires
    • 0 or 1 analogue output
    • Measurements of V, U, I, F, P, Q, S, FP, Tan φ , Cos φ , φFund
    • Adjustable accuracy class from 0.1% to 1% (depending on response time)
    • Adjustable response time from 50ms to 1s
    • Ethernet or RS485 communication option
    • Configuration via TRIADJUST 2 software